Water Quality: Request

Problems intermittent since July 96 with brown/yellow water. Today water from hot side was brown. Test results toay (10/9/96)= mn .01/Fe .02 cold. Hot mn .06/fe.94

History

10/9/1996 05:00:00 Closed by Anonymous

10/9/1996 05:00:00 Anonymous commented on this case.

Took samples for lab test. PH 8.6/Cl2 1.0 mg/L Cold water test for Mn/fe+good. Hot water mn=.06/fe=.94 SG visited. Talked with M. Malone. Plumbing contractor had flushed the hot water heater.They recommended more freq. flushing. Cl2=2.1 ppm 10/11/96-6:30am cl2=1.0mg/L. Hot & cold both clear. Jumper put in Will have Dillman lab test quality at meter daily for one week..

10/9/1996 05:00:00 Opened by Anonymous

10/9/1996 05:00:00 Anonymous inspected this Location

Took samples for lab test. PH 8.6/Cl2 1.0 mg/L Cold water test for Mn/fe+good. Hot water mn=.06/fe=.94 SG visited. Talked with M. Malone. Plumbing contractor had flushed the hot water heater.They recommended more freq. flushing. Cl2=2.1 ppm 10/11/96-6:30am cl2=1.0mg/L. Hot & cold both clear. Jumper put in Will have Dillman lab test quality at meter daily for one week..